Technical indicators
Electrical indicators
External Power ( Power ):
22 - 30VDC , 100mA , upper computer power supply or use TM900 ;
90 - 250VAC ± 20% , 50 - 60Hz , 50mA ;
Frequency Response : ( ± 3dB)
Acceleration: 2.0 - 10KHz ;
Rate of: 10 - 10KHz ;
Bit Shift: 10 - 3.0 kHz ;
Acceleration (low frequency option): 0.5 - 100Hz ;
Speed of the (low frequency Option): for 1.5 - 100Hz ;
Bit shift (low frequency options): 2.0 - 100Hz .
External sensor sensitivity ( sensor ):
100 mV/g , acceleration sensor;
4.0mmV/ μm /s , speed sensor.
External sensor:
24VDC , 4mA constant current.
Terminals:
" A/P " end: Connect the red cable;
" B/S " end: Connect the white cable.
An output buffer ( Buf Out ):
The output of the original signal.
DC bias: 10VDC ;
Output impedance: 100 Ω.
The maximum transmission distance: 300 meters .
Sensitivity: Same as sensor.
Total vibration output ( 4 - 20mA ):
4 - 20mA , active, driving 750 Ω load;
1 - 5V , active, output impedance 250 Ω.
Alarm Set ( Normal/Set ):
Fan Wai: 0 - 100 % of full scale;
Accuracy: ± 0.1 %.
Alarm /Danger :
Seal: Epoxy resin.
Node capacity: 2A /220VAC or 2A /24VDC ; resistive load.
Node type: SPDT, SPDT .
Output isolation: 1000VDC .
Operating status photocell LED indication:
Green light: The system passes self-test and the instrument works normally.
Yellow light: alarm indication;
Red light: Interlocking instructions.
Alarm Reset / Alarm Bypass ( RESET ):
Monitoring table built-in alarm reset button;
Remote alarm reset / alarm bypass terminal (" RESET ").
Physical indicators
shape:
Size: Height: 75mm , other dimensions see the dimensions of the TM table;
Weight: 1000 grams .
Environmental indicators
Operating temperature: -35 0 C to +70 0 C ;
Storage temperature: -40 0 C to +100 0 C .
Wet degree: 95 % Non-coagulated.