    The QUINT POWER power supply 
    QUINT POWER circuit breakers provide maximum functionality and can be quickly thermally decoupled at six times the rated current, providing selective system protection and cost savings. Precautionary function monitoring ensures extremely high system availability because it can issue critical operating status reports before a fault occurs. 
    With the static power reserve POWER BOOST, heavy loads can be reliably started. The adjustable voltage covers all ranges between 5 V DC ... 56 V DC.

    size

    width 60 mm
    height 130 mm
    depth 125 mm
    Spare terminal width 122 mm
    Spare terminal height 130 mm
    Alternate assembly view 63 mm

    Environmental conditions

    Protection level IP20
    Ambient temperature (running) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
    Ambient temperature (debug type test) -40 °C
    Ambient temperature (storage/transportation) -40 °C ... 85 °C
    Maximum relative humidity allowed (operating) ≤ 95 % (no condensation at 25 ° C)
    Anti-interference EN 61000-6-2:2005
    Installation height 5000 m

    Tình trạng sản phẩm:


    Input data

    Rated input voltage range 100 V AC ... 240 V AC
      110 V DC ... 250 V DC
    Input voltage range 85 V AC ... 264 V AC
      90 V DC ... 350 V DC (UL 508: ≤ 300 V DC)
    Maximum dielectric strength 300 V AC
    AC frequency range 45 Hz ... 65 Hz
    DC frequency range 0 Hz
    PE discharge current < 3.5 mA
    Electricity consumption 2.2 A (120 V AC)
      1.3 A (230 V AC)
      2.5 A (110 V DC)
      1.2 A (220 V DC)
    Rated power consumption 257 W
    Shock surge current < 15 A (typical)
    Power failure bypass > 36 ms (120 V AC)
      > 36 ms (230 V AC)
    Input fuse 10 A (slow blow, internal)
    Choose the right fuse 10 A ... 20 A (AC: Characteristics B, C, D, K)
    Protection name Transient surge protection
    Protection circuit/component Varistor, gas discharge tube

    Output Data

    Rated output voltage 24 V DC ±1 %
    Setting range of output voltage (U Set ) 18 V DC ... 29.5 V DC (> 24 V DC, stable capacity limit)
    Rated output current (I N ) 10 A (-25 °C ... 60 °C, U OUT = 24 V DC)
    POWER BOOST (I Boost ) 15 A (-25 ° C ... 40 ° C constant, U OUT = 24 V DC )
    Selective fuse (I SFB ) 60 A (12 ms)
    attenuation 60 °C ... 70 °C (2.5%/K)
    Even Yes, for redundancy and increased capacity
    Concatenation Yes
    Control deviation < 1 % (load change, static 10% ... 90%)
      < 2 % (load change, dynamic 10% ... 90%)
      < 0.1 % (the input voltage varies by ±10%)
    Residual wave < 50 mV SS (rated value)
    Output Power 240 W
    Typical response time < 0.15 s
    Maximum idle power consumption 9.1 W
    Maximum rated load power loss 22 W

    Overview

    net weight 1.1 kg
    effectiveness > 92.5 % (230V AC and rating)
    Insulation voltage input / output 4 kV AC (type test)
      2 kV AC (conventional test)
    Insulation voltage input / PE 3.5 kV AC (type test)
      2 kV AC (conventional test)
    Insulation voltage output / PE 500 V DC (conventional test)
    Protection level I
    MTBF (IEC 61709, SN 29500) > 940000 h (25 °C)
      > 530000 h (40 °C)
      > 230000 h (60°C)
    Installation location Horizontal DIN rail NS35, EN60715
    Assembly instructions Can be installed side by side; horizontal spacing 5 mm, 15 mm for active components, 50 mm vertical spacing

    Connect data, input

    Connection method Pluggable screw connection
    Minimum cross section of rigid wire 0.2 mm2
    Maximum cross section of rigid wire 2.5 mm2
    Flexible wire minimum cross section 0.2 mm2
    Maximum cross section of flexible wire 2.5 mm2
    Minimum wire cross section AWG 16
    Maximum wire cross section AWG 12
    Stripping length 7 mm
    Thread M3

    Connection data, output

    Connection method Pluggable screw connection
    Minimum cross section of rigid wire 0.2 mm2
    Maximum cross section of rigid wire 2.5 mm2
    Flexible wire minimum cross section 0.2 mm2
    Maximum cross section of flexible wire 2.5 mm2
    Minimum wire cross section AWG 16
    Maximum wire cross section AWG 12
    Stripping length 7 mm
    Thread M3

    Signal display connection data

    Minimum cross section of rigid wire 0.2 mm2
    Maximum cross section of rigid wire 2.5 mm2
    Flexible wire minimum cross section 0.2 mm2
    Maximum cross section of flexible wire 2.5 mm2
    Minimum wire cross section AWG 16
    Maximum wire cross section AWG 12
    Thread M3

    Standards and specifications

    Electromagnetic compatibility Comply with the 2014/30/EU Electromagnetic Compatibility Directive
    electric shock 18 ms, 30 g, in each spatial direction (according to IEC 60068-2-27)
    Emission interference EN 55011 (EN 55022)
    Anti-interference EN 61000-6-2:2005
    Connection meets standards CSA
    Standard / procedure EN 61000-4-2
    Contact discharge 4 kV (strength test 2)
    Standard / procedure EN 61000-4-3
    Frequency Range 80 MHz ... 1 GHz
    Test field strength 10 V/m (strength test 3)
    Frequency Range 1.4 GHz ... 2 GHz
    Test field strength 3 V/m (strength test 2)
    Standard / procedure EN 61000-4-4
    Remarks Standard B
    Standard / procedure EN 61000-4-5
    signal 1 kV (strength test 2 - asymmetric)
    Standard / procedure EN 61000-6-3
      EN 61000-4-6
    Frequency Range 0.15 MHz ... 80 MHz
    Voltage 10 V (strength test 3)
    Standard - Electrical Safety IEC 60950-1/VDE 0805 (SELV)
    Standard - electronic equipment used in power installation and assembly of electronic equipment in power installation EN 50178/VDE 0160 (PELV)
    Standard - safe ultra low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
    Standard - safety insulation DIN VDE 0100-410
    Standard - main co-wave current limit EN 61000-3-2
    Standard - Equipment Safety BG (design test)
    Standard - for medical certification IEC 60601-1, 2 x MOOP
    Shipbuilding industry license Germanischer Lloyd (EMC 1), ABS, LR, RINA, NK, DNV, BV
    UL certification UL, UL 508
      UL/C-UL certified UL 60950-1
      UL ANSI/ISA-12.12.01 Class I, Class II, Groups A, B, C, and D (Hazardous Areas)
    DeviceNet certification DeviceNetTM Power Compliance Test
    Vibration (operation) < 15 Hz, amplitude ± 2.5 mm (according to IEC 60068-2-6)
      15 Hz ... 150 Hz, 2.3 g, 90 min.
    Low voltage command Comply with LV Regulation 2006/95/EC
    Certification - for the needs of the semiconductor industry, in line with the mains pressure drop SEMI F47-0706 Certificate of Conformity
    Information Technology Equipment - Security (CB Certification System) CB certification
    Track application EN 50121-4
    Surge voltage category (EN 62477-1) III 
         

     



    TÂN THÀNH CAM KẾT

    • Sản phẩm, hàng hóa chính hãng.
    • Giá cả cạnh tranh.
    • Dịch vụ chăm sóc khách hàng tận tâm.

    Thông Tin Công Ty

    Đã thông báo

     


    THÔNG TIN LIÊN HỆ:
    CÔNG TY TNHH THIẾT BỊ CÔNG NGHIỆP TTH
    Trụ sở: số 124 ngõ 79 Yên Hoà-Cầu giấy-HN
    Kinh doanh 1 : 0888.868.515 Kinh doanh 2 : 0816.861.515
    Kinh doanh 3 : 0836.861.515 Kinh doanh 4 : 0916.861.515
    Kinh doanh 5 : 0926.511.515 Kinh doanh 6 : 0917.971.515
    Website: http://tanthanhtech.com
    Website: https://vienthongtanthanh.com
    Email: tthkinhdoanh@gmail.com
    Email: tthkinhdoanh01@gmail.com

  • Kết nối với chúng tôi